Phenolic Panel Cladding with XPS Ultra Continuous Insulation & Metal Stud Backup

 

 

 

 

Assembly:

 ComponentManufacturerProduct
 Interior Finish (vapor permeable)--
 Interior Gypsum Board (Type X) -
 Metal Stud (18 GA. Min. @16” O.C.)- -
 Stud Cavity Insulation (Optional)Dow2" Styrofoam CM-2045 SPF
 Exterior Gypsum Sheathing* - -
 Self Adhered Air/Water/Vapor Barrier**Carlisle705 FR-A
 Continuous Insulation**Dow2 1/2" Styrofoam Ultra XPS
 Cladding Attachment System**Knight WallHCI System
 Phenolic Panel Cladding**FiberesinStonewood Architectural Panels

* For a 1 hour fire rating change Exterior Gypsum Sheathing to Fire Rated Exterior Gypsum Sheathing.

** Product recommendations are based on Type I-V construction not requiring NFPA 285 assembly acceptance criteria compliance.

Assembly Performance:

(proposed clear wall U-Factors are approximately 8% | 30% better than code and have 92% | 81% thermal effectiveness)

 Clear Wall

Code Minimum
(IECC 2015 - Metal Framed)

Proposed

Design R-Value: aR-13 + R-7.5ciR-14ci  |  R-12.8 + R-14ci
Total R-Value:N/AR-19.30  |  R-32.10
Effective R-Value:cN/AR-17.73  |  R-26.05
Design U-Factor: a, bU-0.064U-0.059  |  U-0.045
Effective U-Factor: cN/AU-0.056  |  U-0.038
Assembly Air Permeability0.04 cfm/ft2 @75Pa0.0014 cfm/ft2 @75Pa

Clear wall meets energy code thermal requirements without stud cavity insulation.

Clear wall U-Factor is based on the stud size & spacing noted above and is calculated per IECC 2015 & ASHRAE 90.1-2013 Appendix A.

c Clear wall effective thermal performance is based on the stud size & spacing noted above, manufacturer literature and industry studies on the thermal performance of facades.

 